Detail Megger MFT1735 Multifunction Tester
Megger MFT1735 Multifunction Tester
SPECIFICATIONS
Insulation test
Output voltage -0% + 20% at rated load or less
Voltage display ± 3% ± 3 digits ± 0.5% of rated voltage
Short circuit current 1.5 mA nominal test current
Test current on load 1 mA at min pass values of insulation
Measurement accuracy
1000 Volts 10 k© ~ 999 M© ± 3% ± 2 digits
500 Volts 10 k© ~ 500 M© ± 3% ± 2 digits
> 500 M© ± 10% ± 4 digits
250 Volts 10 k© ~ 250 M© ± 3% ± 2 digits
> 250 M© ± 10% ± 4 digits
100 Volts 10 k© ~ 100 M© ± 3% ± 2 digits
> 100 M© ± 10% ± 4 digits
Continuity / resistance
0.01 © ~ 99.9 © ± 2% ± 2 digits
100 © ~ 99.9 k© ± 5% ± 2 digits
Open circuit voltage 5 V ± 1 V
Test current ( 0 © ~ 2 © ) 205 mA ± 5 mA
15 mA ± 5 mA ( user selectable)
Loop test
Live to earth supply 48 V ~ 280 V ( 45 Hz ~ 65 Hz)
Live to live supply 48 V ~ 500 V ( 45 Hz ~ 65 Hz)
L-N/ L-L tests ± 5% ± 3 digits
L-E tests*
0.1 © ~ 39.9 © ± 5% ± 5 digits ± noise margin
40.0 © ~ 999 © ± 10% ± 5 digits
Display range 0.01 © ~ 999 ©
Live to earth PFC range 20 kA
Live to live PSCC range 20 kA
Rcd tests
Supply up to 100 mA 48 V ~ 480 V ( 45 Hz ~ 65 Hz)
Supply up to 1 A 48 V ~ 280 V
RCD type Type AC, A, S
Type B ( pure dc)
No trip test ( 1/ 2xI) – 10% ~ – 0%
Trip test ( 1xI & 5xI) + 0% ~ + 10%
Ramp test
Touch voltage ( 0 ~ 253 V) + 5% + 15% ± 0.5 V
Trip time ± 1% ± 1 ms
Trip current ± 3%
Step increments
VAR ( variable RCD selection) 10 mA ~ 50 mA 1 mA steps
50 mA ~ 500 mA 5 mA steps
500 mA ~ 1000 mA 10 mA steps
Supply measurement
Voltage 10 V ~ 600 V ( 15 ~ 400 Hz) True
RMS
± 3% ± 1 V ± 2 digits
Phase rotation indication L1– L2– L3 & L1– L3– L2
Frequency 15 Hz ~ 99 Hz ± 0.5% ± 1 digit
100 Hz ~ 400 Hz ± 2.0% ± 2 digits
Frequency resolution 0.1 Hz
Tampilkan Lebih Banyak